FLW20006 - Recirculating Cooler

Download

FLW20006 - Recirculating Cooler

Technical Data;
Working temperature range (°C) : -25 ... +40
Temperature stability (°C) : ±0.5
Setting / display resolution : 0.1 °C
Temperature Display : LED
Cooling capacity (Medium Ethanol) @ 20 °C : 20 kW
Pump capacity flow rate (l/min) : 80
Pump capacity flow pressure (bar) : 0.8-6.0
Pump connections : G1 1/4"
Barbed fittings diameter (inner dia. / mm) : 1"
Filling volume (liters) : 15 ... 37
Refrigerant stage 1 : R452A
Filling volume refrigerant stage 1 (g) : 2750
Global Warming Potential for R452A : 2140
Carbon dioxide equivalent stage 1 (t) : 5.885
Digital interfaces : RS232
Optional : Profibus
Ambient temperature : 5...40 °C
Dimensions W x L x H (cm) : 95 x 115 x 161
Weight (kg) : 360
Sound pressure level (distance 1 m) max. (dBA) : 69
Description Suitable fluids: water, water-glycol mixture, JULABO Thermal bath fluids.
Cooling of compressor : Water